Diagnosing Disk-Space Variation in Transformer Windings Using High-Frequency Inductance Measurement
Abstract:
Leakage and magnetizing inductances of transformer windings are routinely measured by power utilities during scheduled maintenance. They are often used to confirm the diagnosis of mechanical damages in windings after Swept Frequency Response Analysis shows a mismatch. Inductance measurements performed at power frequency can possibly reveal the presence of damages that have substantially progressed but cannot detect them at their nascent stages since inductances at power frequency remain almost unaltered. This paper investigates the possibility of using high-frequency inductance to this end considering a frequently encountered mechanical damage, viz., disk-space variation in a disk winding. Effect of disk-space variation is investigated in this article using FEM at first and inductances at different frequencies are considered: magnetizing and leakage inductances at 50 Hz, and inductance at a higher frequency region corresponding to winding resonances, say, 500 kHz. The inductance at high frequencies not only exhibited increased sensitivity compared to that at power frequency, but also captured the extent of damage. Simulations performed using Ansys Maxwell and experimental results on an actual 1-phi transformer are reported. Results show that the high-frequency inductance not only offers a considerably increased sensitivity to disk-space variation in windings compared to the power frequency inductances, but also provides insight regarding the extent of movement which is not apparent from the frequency response.
Año de publicación:
2022
Keywords:
- TRANSFORMERS
- condition monitoring
- inductance measurement
- Resonance
- fre- quency response
Fuente:
Tipo de documento:
Article
Estado:
Acceso restringido
Áreas de conocimiento:
Áreas temáticas:
- Física aplicada
- Otras ramas de la ingeniería
- Ingeniería y operaciones afines