Evaluación del Índice de Salud de transformadores de potencia mediante el uso de lógica difusa y variables mínimas de uso común
Abstract:
This paper proposes a fuzzy logic analysis model that allows assessing power transformers Health Index (HI), taking into account minimum variables that are commonly used in this kind of analysis. For each input variable, the membership degrees are defined according to expert criteria. It is started from a proposed model then a sensitivity analysis is carried out to verify how the system inputs omission affects Health Index. The results show that acidity and dissipation factor can be leaved out in a proposed system that considers six input variables, without affecting the calculated transformer health index, significantly.
Año de publicación:
2022
Keywords:
Fuente:
googleTipo de documento:
Other
Estado:
Acceso abierto
Áreas de conocimiento:
- Lógica difusa
Áreas temáticas de Dewey:
- Física aplicada
- Programación informática, programas, datos, seguridad
- Otras ramas de la ingeniería
Objetivos de Desarrollo Sostenible:
- ODS 9: Industria, innovación e infraestructura
- ODS 17: Alianzas para lograr los objetivos
- ODS 7: Energía asequible y no contaminante