Ferroresonance in subharmonic 3rd mode in an inductive voltage transformer, a real case analysis
Abstract:
This paper focuses on a ferroresonance incident in subharmonic 3rd mode captured in the electrical substation Rio Escondido (REC), in the northeast of Mexico. Bearing in mind that this kind of ferroresonance phenomenon is a sporadic event and difficult to record, the contribution of this paper consists of the analysis of this real-life ferroresonance phenomenon and to propose a practical solution that prevents these kinds of incidents. An analytical calculation to obtain the electrical parameters of a damping reactor used to damp out the ferroresonance phenomenon registered in the REC substation is reported. © 2014 Elsevier Ltd. All rights reserved.
Año de publicación:
2014
Keywords:
- Damping reactor
- Inductive voltage transformer
- Subharmonic 3rd mode
- Ferroresonance
Fuente:
scopus
Tipo de documento:
Article
Estado:
Acceso restringido
Áreas de conocimiento:
Áreas temáticas:
- Física aplicada