Operating capability as a PQ/PV node of a direct-drive wind turbine based on a permanent magnet synchronous generator


Abstract:

This paper describes the modelling and control system of a direct-drive PMSG wind turbine for effective active and reactive power generation control and voltage control at the grid connection point. This study focuses on the maximum power capability of the wind turbine, which is limited by its generator and power converter. The ability of this model and control strategy are assessed by means of simulations and discussed at length. The results of our study show that a PMSG wind turbine is able to actively participate in grid operation because it can independently control active and reactive power production (operating as a PQ node) or the active power and voltage at the connection node (operating as a PV node). © 2009 Elsevier Ltd. All rights reserved.

Año de publicación:

2010

Keywords:

  • wind turbine control
  • Wind turbine modelling
  • Permanent magnet synchronous generator (PMSG)

Fuente:

scopusscopus

Tipo de documento:

Article

Estado:

Acceso restringido

Áreas de conocimiento:

  • Energía renovable
  • Energía

Áreas temáticas:

  • Física aplicada