Study of liquid injection impact on the performance of new refrigerant mixtures


Abstract:

In this paper, the test results of liquid injection impact on the performance of new alternative refrigerant mixtures such as: R-410A, R-507, R-407C and R-404A are discussed, analysed and presented. The test results were obtained using an air-source heat pump set-up with enhanced surface tubing under various liquid injection ratios. Performance tests were conducted according to the ARI/ASHRAE standards. The performance data demonstrated that as liquid injection ratio increases, compressor head pressure and discharge temperature decrease. This has a positive effect in protecting the compressor. The effect of liquid injection on mixture behaviour varies from one mixture to another depending upon the mixture's composition. Furthermore, liquid injection appears to have a significant influence on R-410A behaviour compared to the other mixtures in question. © 2002 John Wiley & Sons, Ltd.

Año de publicación:

2003

Keywords:

  • New refrigerant mixtures
  • ARI/ASHRAE standards
  • Liquid injection impact

Fuente:

scopusscopus

Tipo de documento:

Article

Estado:

Acceso abierto

Áreas de conocimiento:

  • Energía
  • Ingeniería química

Áreas temáticas:

  • Física aplicada